Confirmation
If the SMS Relay does not receive a confirmation SMS within a certain preset time from the receiver, the event
message will be sent to the next receiver. This means that the device runs through the 5 allocated receiver
numbers and restarts afterwards with the first number again (The number of running loops can be
pre-defined). As soon as the device receives a confirmation from the receivers the process is stopped. If this
is not the case the message will be sent to the next receiver (after expiry of the preset time). if the
acknowledgement is inactive, all receivers who are allocated to that event will receive a message without
repetition. If the confirmation code word is not activated, the phone number identification is carried out as a
security check and it is sufficient to send an empty SMS message to the x-Messenger SMS Relay.
5.7.3.3 Message delay
If the message criteria are reached, the respective message transmission can be time delayed, i.e. the SMS
relay only sends the pre-defined message after the preset time has elapsed and if the value has remained
constantly during that time. In other words, the measured value is ignored during the set delay time. Time
delays of 0.1 seconds to 99.9
hours are possible. This time function default must be activated and is to prevent that unstable short signals
can activate numberless identical SMS messages.
REMARK
It is recommended to use the delay function to avoid several messages being sent for the same
event.
5.7.3.4 Message block
If message criteria are reached, which requires sending of a message, a timer is triggered. There will be no
further message (same messages) sent during that pre-set time. With that setting it can be avoided that the
same status message is sent repeatedly during a set time (Block time).
REMARK
It is recommended to use the delay function to avoid several messages being sent for the same
event.