102 Rockwell Automation Publication 2080-UM002M-EN-E - April 2022
Chapter 6 Micro870 Controller Distributed Network Protocol
FREEZE_CLEAR_NR (FC Byte = 0x0A)
10 – Freeze and Clear No Resp
See FREEZE_CLEAR (FC Byte = 0x09)
. No response message is returned when
this request is issued from a DNP3 master.
COLD_RESTART (FC Byte = 0x0D)
13 – Cold Restart
This function code forces the controller to perform a complete restart upon
powering up.
WARM_RESTART (FC Byte = 0x0E)
14 – Warm Restart
This function code forces the controller to perform a partial reset.
INITIALIZE_APPL (FC Byte = 0x10)
16 – Initialize Application
This function code is used to initialize the user program which was
downloaded by Connected Components Workbench software.
START_APPL (FC Byte = 0x11)
17 – Start Application
This function code is used to start the user program which was downloaded by
Connected Components Workbench software.
STOP_APPL (FC Byte = 0x12)
18 Stop Application
This function code is used to stop the user program which was downloaded by
Connected Components Workbench software.
ENABLE_UNSOLICITED (FC Byte = 0x14)
20 – Enable Unsolicited Message
This function is used to dynamically enable unsolicited messages generated in
the controller.
DISABLE_UNSOLICITED (FC Byte = 0x15)
21 – Disable Unsolicited Message
This function is used to dynamically disable unsolicited messages generated in
the controller.
DELAY_MEASURE (FC Byte = 0x17)
23 – Delay Measurement, used for Non-LAN Procedure
This function code is used to measure the communication channel delay time.