Rockwell Automation Publication 2080-UM002M-EN-E - April 2022 73
Chapter 5 Communication Connections
The valid range of static IPv4 IP address exclude:
• Broadcast or zero IP (255.255.255.255 or 0.0.0.0)
• IP address starting with 0 or 127 (0.xxx.xxx.xxx or 127.xxx.xxx.xxx)
• IP address ending with 0 or 255 (xxx.xxx.xxx.0 or xxx.xxx.xxx.255)
• IP addresses in range 169.254.xxx.xxx (169.254.0.0 to 169.254.255.255)
• IP addresses in range 224.0.0.0 to 255.255.255.255
Ethernet Host Name
Micro800 controllers implement unique host names for each controller, to be
used to identify the controller on the network. The default host name is
comprised of two parts: product type and MAC address, separated by a
hyphen. For example: 2080LC50-xxxxxxxxxxxx, where xxxxxxxxxxxx is the
MAC address.
The user can change the host name using the CIP Service Set Attribute Single
when the controller is in Program/Remote Program mode.
Configure CIP Serial Driver 1. Open your Connected Components Workbench project. On the device
configuration tree, go to the Controller properties. Click Serial Port.
2. Select CIP Serial from the Driver field.
3. Specify a baud rate. Select a communication rate that all devices in your
system support. Configure all devices in the system for the same
communication rate. Default baud rate is set @ 38,400 bps.
4. In most cases, parity and station address should be left at default
settings.
5. Click Advanced Settings and set Advanced parameters.
OPC Support Using
FactoryTalk Linx
Support for Open Platform Communications (OPC) using CIP symbolic has
been added from firmware release 7.011 onwards. This can be used in place of
Modbus addressing.
FactoryTalk® Linx software version 5.70 (CPR9 SR7) or later and FactoryTalk®
Linx Gateway software version 3.70 (CPR9 SR7) or later are required.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation Allen-Bradley Micro820 and is the answer not in the manual?

Rockwell Automation Allen-Bradley Micro820 Specifications

General IconGeneral
BrandRockwell Automation
ModelAllen-Bradley Micro820
CategoryController
LanguageEnglish

Related product manuals