V-168
Control Systems
6
6
Building management system
6-1. Lonworks interface module (MIM-B07)
4) Function
Control and monitoring
SNVT configuration
Control
Monitoring
Function
On/Off
Set operation mode
Set temperature
Set fan speed
On/Off
Operation mode
Room temperature
Error
Description
Operation on/off
Auto/Cool /Heat /Fan
Cooling mode :18~30°C,
Heating mode :16~30°C
Auto /Low/Middle /High
Indoor unit’s operation on/off status
Operation mode status
Current room temperature
Error occurrence status, Error code
NV name
nviIndoorMode [12]
nviSetTemp [12]
nviFanSpeed [12]
nvoIndoorStatus [12]
nvoRoomTempm [12]
NV type
SNVT_hvac_mode
SNVT_temp_f
SNVT_Switch
SNVT_hvac_Status
SNVT_temp_f
Description
On/Off status and operation mode setting
Temperature setting
Fan speed setting
On/Off, Mode, Error monitoring
Current room temperature monitoring
Index
2~13
14~25
26~37
38~49
50~61
No.
(1)
(2)
(3)
(4)
(5)
DVM Indoor [12 ]
nviIndoorMode
nvoRoomTemp
nvoIndoorStatus
nviSetTemp
nviFanSpeed
05-4~6_control systems(142~171 3/6/08 14:09 Page 168