EasyManua.ls Logo

Samsung DVM PLUS III - Page 701

Samsung DVM PLUS III
748 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
V-169
C
ONTROL
S
YSTEMS
5) Installation
(1) nviIndoorMode
(2) Setting temperature range : Cooling mode 18 ~ 30°C, Heating mode 16 ~ 30°C
(3) nviFanSpeed
SNVT_hvac_mode
HVAC_OFF
HVAC_Auto
HVAC_COOL
HVAC_HEAT
HVAC_FAN_ONLY
Operation
OFF
ON
ON
ON
ON
DVM operation mode
Last operation mode
Auto mode
Cooling mode
Heating mode
Fan mode
(4) nvoIndoorStatus
Field
Mode
Heat_output_primary
Fan_output
In_alarm
Type
Hvac_t
Signed long
Signed long
Unsigned short
Description
On/Off, Operation mode
Indoor unit address
Error code
Error occurrence (True/False)
State
Any
Value
0 (Default)
1
2
3
Operation
Auto
Low
Middle
High
CPU : Neuron 3150 Smart Transceiver
Communication : RS485 to FTT-10A
Transmission speed : FTT-10A 78Kbps
Wiring : Free topology (Non-polarity)
Supports SNVT for BMS interface
Supports auto-binding mode
Power supply : DC 12V
Max. 4 Lonworks interface modules can be connected to 1 outdoor unit.
(12 indoor units per 1 Lonworks interface module)
Specification