S&C Instruction Sheet 461-504 57
Informational and Settings Screens
Open Interval and O/C Sequence Time
If the reclosing sequence consists of just the Initial Trip operation (i.e., single shot to
lockout), the reset time does not need to be entered. If there are two or more trip opera-
tions, the open interval must be entered between adjacent trip operations in addition to
the reset time. On the screen, the setting eld for the Open Interval setting is located
between two adjacent trip operations; the eld for the O/C Sequence Time setting is
always located at the end of all trip operations. See Figure 80.
Figure 80. The Open Interval and O/C Sequence Time setting field locations.