58 S&C Instruction Sheet 461-504
Informational and Settings Screens
Open Interval following Initial Trip, Test 1, or Test 2. Specify interrupter open
time (in seconds) before it recloses after the initial Trip operation, after Test 1, or after
Test 2, as applicable (minimum value: 0.5; maximum value: 5 [or 30 for extended open
interval-capable reclosers]).
O/C Sequence Time. Specify the reset time for the test sequence, in seconds (minimum
value: 0.5; maximum value: 1000). If a TripSaver II recloser remains closed upon comple-
tion of an action in the test sequence—and the overcurrent element has not picked up
and started timing again within this setting—the test sequence counter will reset and
the TCC curve will reset to its setting dened in the Trip operation.
Note: An active O/C Sequence Time timer will not expire after a TripSaver II recloser
loses power. It will continue counting down until the defined duration has been reached.
Default TCC Curve Settings
The software launches with a set of default TCC curve settings that match those pro-
grammed into every standard TripSaver II recloser before it leaves the factory. This is
the starting point of the conguration process. The S&C default TCC curve settings are
shown below:
Initial Trip: Microprocessor Recloser S&C 104 curve; Minimum Trip Current: 100 A;
Time Multiplier: x1; Reset Type: D/T (Denite Time); Reset Time: 0.1s; Advanced TCC
Curve Setup: Off.
Open Interval After Initial Trip: 5s.
Sequence Coordination (Disabled): Microprocessor Recloser S&C 133 curve;
Minimum Trip Current: 100 A; Time Multiplier: x2; Reset Type: D/T (Denite Time); Reset
Time: 0.1s; Advanced TCC Curve Setup: Off.
Coordination Reset Time: 120s.
Test 1: Microprocessor Recloser S&C 104 curve; Minimum Trip Current: 100 A; Time
Multiplier: x1; Reset Type: D/T (Denite Time); Reset Time: 0.1s; Advanced TCC Curve
Setup: Off.
Open Interval After Test 1: 5s.
Test 2: Microprocessor Recloser S&C 133 curve; Minimum Trip Current: 100 A; Time
Multiplier: x2; Reset Type: D/T (Denite Time); Reset Time: 0.1s; Advanced TCC Curve
Setup: Off.
Open Interval After Test 2: 5s.
Test 3: Microprocessor Recloser S&C 133 curve; Minimum Trip Current: 100 A; Time
Multiplier: x2; Reset Type: D/T (Denite Time); Reset Time: 0.1s; Advanced TCC Curve
Setup: Off.
O/C Sequence Time: 15s.
These default settings for the setup software used while in the Standalone (of ine)
mode can be changed in the Standalone tab under the Options feature. See the
Options feature under the Tools menu.