86 S&C Instruction Sheet 461-504
Informational and Settings Screens
General Device Information
The “General Device Information” section is collapsed by default. The section can be
expanded by clicking on the green title located at the bottom part of the Status screen.
See Figure 121.
Figure 121. The General Device Information area.
When expanded, the following hardware and firmware related information of the
connected TripSaver II recloser are displayed:
Hardware
Voltage Rating (Max), kV. This indicates the rated maximum voltage of the connected
TripSaver II recloser. Either 15.5 kV or 29 kV is displayed.
Continuous Current Rating, A. This indicates the continuous current rating of the
connected TripSaver II recloser. This value will be either 100 A or 200 A.
Interrupting Rating, Symm., kA. This indicates the interrupting rating in symmetrical
kiloamps of the connected TripSaver II recloser. Either 4 kA or 6.3 kA is displayed.
System Frequency, Hz. This indicates the frequency of the electrical system the con-
nected TripSaver II recloser was congured to operate on by the factory. Either 50 Hz or
60 Hz is displayed.
Serial Number. This indicates the serial number of the connected TripSaver II recloser.