VC 1100 List of Setup Parameters
VC1100E/paralist Version 2
© Schenck VIBRO GmbH, D-64273 Darmstadt, Juni 98 C01 / C02 - C11 / C12 5-13
J 07 Channel A : Signal Setection Type
Choises : rms, pc, ppc
rms = Root-mean-square value
pc = Zero-to-peak calculated value
ppc = Peak-to-peak calculated value
J 08 Channel B : Signal Setection Type
Choises : rms, pc, ppc
s = Root-mean-square value
pc = Zero-to-peak calculated value
ppc = Peak-to-peak calculated value
J 09 Channel A : Full scale (Vibration)
Range : 0.200 ... 999
Resolution : 0.200 ... 0.999
1.00 ... 9.99
10.0 ... 99.9
100 ... 999
Function : Define full scale value for the measured vibra-
tion parameter of channel A. You can use diffe-
rent full scale values for channel A and B.
VIBROCONTROL 1100 uses the full scale values to automatically
configure the analog circuits, display functions, monitoring functi-
ons, and the analog outputs.
If you enter full scale values outside the ranges defined in the ta-
ble, the consistency check generates error message -62.
J 10 Channel B : Full scale (Vibration)
Range : 0 ... 999
Resolution : 0.200 ... 0.999
1.00 ... 9.99
10.0 ... 99.9
100 ... 999
Function : Define full scale value for the measured vibra-
tion parameter of channel B. You can use diffe-
rent full scale values for channel A and B.
For more information see parameter J09