List of Setup Parameters VC 1100
Version 2 → parqalist/VC1100E
5-14 C01 / C02 - C11 / C12 © Schenck VIBRO GmbH, D-64273 Darmstadt, Juni 98
J 11 Channel A : Bearing condition (BCU)
Choises : Y, N
Function : Enable or disable processing of BCU values for
channel A
Y = Process BCU for channel A.
N = Do not process BCU for channel A.
Connect an accelerometer to channel A to measure BCU.
J 12 Channel B : Bearing condition (BCU)
Choises : Y, N
Function : Enable or disable processing of BCU values for
channel B.
Y = Process BCU for channel B.
N = Do not process BCU for channel B.
Connect an accelerometer to channel B to measure BCU.
J 13 Channel A : BCU Full scale:
Range : 1 ... 140
Resolution : 1,00 ... 9,99
10,0 ... 99,9
100 ... 140
Function : Define full scale value for BCU on channel A.
VIBROCONTROL 1100 uses the full scale value to automatically
configure the BCU Signal Conditioner, display functions, monito-
ring functions, and the analog outputs.
You can use different full scale values for channel A and B. If you
enter a value outside the defined range, the consistency check
generates error-message: -62.
J 14 Channel B : BCU Full scale
Range : 1 ... 140
Resolution : 1,00 ... 9,99
10,0 ... 99,9
100 ... 140
Function : Define full scale value for BCU on channel B.
VIBROCONTROL 1100 uses the full scale value to automatically
configure the BCU Signal Conditioner, display functions, monito-
ring functions, and the analog outputs.
You can use different full scale values for channel A and B. If you
enter values outside the defined range, the consistency check ge-
nerates error-message: -62.