PMCM-9340D-0208 ACCESS 9340 and 9360 Meters
2/2008 Appendix A—Meter Register List
EN–163
Analog Input Template
Base IO Point Type — — 300 – 399
• First digit (3) = point is analog input
• Second digit = range of analog I/O values
(used without units)
0 = 0 – 1
1 = 0 – 5
2 = 0 – 10
3 = 0 – 20
4 = 1 – 5
5 = 4 – 20
6 = -5 – 5
7 = -10 – 10
8 = -100 – 100
9 = User defined (values default to 0)
• Third digit = digital resolution of the I/O
hardware. The user must select from one of
these standard ranges.
0 = 8-Bit, unipolar
1 = 10-Bit, unipolar
2 = 12-Bit, unipolar
3 = 14-Bit, unipolar
4 = 16-Bit, unipolar
5 = 16-Bit, bipolar with sign
6 = reserved
7 = reserved
8 = Resolution for IO2222 Voltage range 0 -
4000
9 = Resolution for IO2222 Current range
800 - 4000
Base +1 IO Point Label — — ASCII 16 Characters
Base +9 Units Code — — 0 – 99
Placeholder for a code used by software to
identify the SI units of the analog input being
metered, i.e. kW, V, etc.
Base +10 Scale Code — — -3 – 3
Placeholder for the scale code (power of 10)
used by software to place the decimal point.
Base +11 Range Select — — 0 – 1
Analog input gain select. Applies only to Option
Module 2222.
1 = Use calibration constants associated with
current (Default)
0 = Use calibration constants associated with
voltage
Base +12 Analog Input Minimum — — 0 – ±32,767
Minimum value of the scaled register value for
the analog input. (Only if Metering Register
Number is not 0.)
Base +13 Analog Input Maximum — — 0 – ±32,767
Maximum value of the scaled register value for
the analog input. (Only if Metering Register
Number is not 0.)
Table A–4: Registers for Inputs and Outputs
Reg Name Scale Units Range Notes