2/2008 Appendix A—Meter Register List
EN–165
Analog Output Template
Base IO Point Type — — 400 – 499
• First digit (4) indicates point is analog output
• Second digit indicates the range of analog
I/O values (used without units)
0 = 0 – 1
1 = 0 – 5
2 = 0 – 10
3 = 0 – 20
4 = 1 – 5
5 = 4 – 20
6 = -5 – 5
7 = -10 – 10
8 = -100 – 100
9 = User defined (values default to 0)
• Third digit indicates the digital resolution of
the I/O hardware. The user must select from
one of these standard ranges.
0 = 8-Bit, unipolar
1 = 10-Bit, unipolar
2 = 12-Bit, unipolar
3 = 14-Bit, unipolar
4 = 16-Bit, unipolar
5 = 16-Bit, bipolar with sign
6 = reserved
7 = reserved
8 = Resolution for IO2222 Voltage range 0 -
4000
9 = Resolution for IO2222 Current range
800 - 4000
Base +1 IO Point Label — — ASCII 16 Characters
Base +9 Reserved — — — Reserved for future development
Base +10 Reserved — — — Reserved for future development
Base +11 Reserved — — — Reserved for future development
Base +12 Output Enable — — 0 – 1
0 = Enable (default)
1 = Disable
Base +13 Reserved — — — Reserved for future development
Base +14
Lower Limit Analog
Value
— — 0 – ±327
Lower limit of the analog output value. Default
value based on I/O Point Type.
Base +15
Upper Limit Analog
Value
— — 0 – ±327
Upper limit of the analog output value. Default
value based on I/O Point Type.
Base +16
Lower Limit Register
Value
— — 0 – ±32,767
Lower limit of the register value associated with
the lower limit of the analog output value.
Base +17
Upper Limit Register
Value
— — 0 – ±32,767
Upper limit of the register value associated with
the upper limit of the analog output value.
Base +18
Reference Register
Number
— — 1000 – 32000
Register location of value upon which to base
the analog output.
Table A–4: Registers for Inputs and Outputs
Reg Name Scale Units Range Notes