© 2008 Siemens Energy & Automation, Inc. All Rights Reserved
PMCM-9340D-0208 ACCESS 9340 and 9360 Meters
2/2008 Appendix C—EN50160 Evaluation
EN–219
APPENDIX C—EN50160 EVALUATION
This section applies to the following models ACCESS 9360 and it
describes how the ACCESS 9360 operates when the European
standard EN50160 evaluation feature is enabled. For instructions on
how to enable the evaluation feature, see “Setting Up EN50160
Evaluation from the Display” on page 239.
Overview
EN50160:2000 “Voltage characteristics of electricity supplied by
public distribution systems” is a European standard that defines the
quality of the voltage a customer can expect from the electric utility.
Although this is a European standard, it can be applied in the U.S.
The ACCESS 9360 evaluates the following electrical characteristics
in accordance with EN50160:
Table C1: EN50160 Evaluation for the ACCESS 9360
Feature 9360
Evaluation During Normal Operation (Meter-based Data)
Frequency
Supply voltage variations
Supply voltage unbalance
Harmonic voltage
Total Harmonic Distortion
Evaluations During Abnormal Operations (Alarm-based Data)
Magnitude of rapid voltage changes
Supply voltage dips
Short interruptions of the supply voltage
Long interruptions of the supply voltage
Temporary power frequency overvoltages
The ACCESS 9360 performs EN50160 evaluations on disturbance alarms.
Must be configured using register writes. See Table C4 on page 229 for a list of
configuration registers.