Connection
7.3 Connection of Siemens SENTRON switching devices
3KC ATC6500 transfer control device
106 Manual, 05/2019, L1V30538268002A-01
Key features of the 3VA27
Rated operational voltage U
e
AC 50 / 60 Hz [V AC] 600
1
Rated operational current In at 50 °C ambient temperature
Rated operational frequency
Short-time withstand current I
cw
Impulse withstand voltage (U
imp
) of the main circuit
Impulse withstand voltage (U
imp
1
Due to maximum nominal voltage U
n
of the ATC6500 controller of 600 V AC
Key features of the 3WL10 and FSI-III
Rated operational voltage U
e
AC
[V AC] 600
1
600
1
600
1
600
1
Rated operational current I
n
at
50 °C ambient temperature
[A] 630 ... 1250 1000 ... 2000 800 ... 4000 4000 ... 6300
Rated operational frequency
Short-time withstand current I
cw
[kA] 42 - 50
2
42 - 85
2
50 - 100
2
85 - 130
2
Impulse withstand voltage (U
imp
)
[kV] 12 12 12 12
Impulse withstand voltage (U
imp
)
[kV] 2.5 2.5 2.5 2.5
Due to maximum rated voltage U
n
of the ATC6500 controller of 600 V AC
Dependent on the breaking capacity of the 3WL. You will find more information in the relevant documentation of the
Key features of the 3WT:
Rated operational voltage U
e
AC 50 / 60 Hz [V AC] 500
Rated operational current In at 50 °C ambient temperature
Rated operational frequency
Short-time withstand current I
cw
1
Impulse withstand voltage (U
imp
) of the main circuit
1
applies to Ecoline. You can find more information in the manual of the 3WT air circuit breaker.