Parameterization
9.4 Parameters
3KC ATC6500 transfer control device
162 Manual, 05/2019, L1V30538268002A-01
9.4.2 P02 - General
P02
Designation on ATC
display
Description
Unit
Default
Range
P02.01
LAYOUT
System configuration
This parameter enables the system configuration
to be set. The various applications can be selected
with and without a tie breaker. For the description of
the applications, see chapter
Load management
with the ATC6500 (Page 20).
A: 2S/0T A: 2S/0T
B: 2S/1T/PL
C: 2S / 1T / SI
D: 2S / 1T / AI
O: 2S / NPL
P02.02
NOMINAL VOLTAGE
Nominal voltage of the plant
The nominal voltage of the power supplies must
be specified here.
Note:
In the case of polyphase systems, always
specify the line-to-line voltage (L-L).
V 400 400-50000
P02.03
VT USED
Use of a voltage transformer VT
This parameter specifies whether a voltage trans-
former is used at the measuring inputs.
OFF OFF/ON
P02.04
VT PRIMARY
Primary circuit of voltage transformer
The primary circuit of a possible voltage trans-
former is defined here.
V 100 50-50000
P02.05
VT SECONDARY
Secondary circuit of voltage transformer
The secondary circuit of a possible voltage trans-
former is defined here.
V 100 50-500
P02.06
PHASE SEQUENCE
Phase sequence check
This parameter enables the checking of the phase
sequence.
OFF = no check
Direct = L1/L2/L3.
Reversed = L3/L2/L1.
Note:
Enable the corresponding alarms for this as
well.
OFF OFF
L1/L2/L3
L3/L2/L1
P02.07
CONNECTION TYPE
Connection type
The type of the existing system is defined here:
Three-phase with neutral conductor L1 L2 L3 / N
Three-phase without neutral conductor L1 L2 L3
Two-phase L1 N L2
Single-phase L1 – N
L1/L2/L3/
N
L1/L2/L3/N
L1/L2/L3
L1/N/L2
L1/N
P02.08
VOLTAGE CONTROL
Selecting the voltage measurement
This defines how the voltage measurement is to
be performed. You can select from the measure-
ment of the line-to-line voltage, the phase voltage,
or both at the same time.
L/L L/L
L/N
L/L + L/N
P02.09
NOMINAL
FREQUENCY
Nominal frequency of plant
The nominal frequency of the power supplies is
defined here.
50 Hz 50 Hz
60 Hz