Parameterization
9.4 Parameters
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01
179
Designation on
ATC display
AUTO TEST
– Duration of the periodic test in minutes.
min 10 1-600
AUTO TEST
WITH LOAD
Automatic TEST with load transfer
– Load management during performance of the periodic test:
OFF = The load is not transferred.
Load = Enables load transfer from the network to the generator.
Dummy load = Load simulation is activated; the system load is not
OFF OFF
Load
Dummy
load
9.4.12 P12 - Digital Inputs
This menu is divided into 20 sections. These refer to 8 possible digital inputs INP1…INP8
that can be managed directly by the ATC6500, and a further 12 inputs that can be managed
by the ATC6500 via the expansion modules.
Designation on ATC
display
INPUT FUNCTION
Function of the input INPn
– Selects the function of the selected input (see
table "Functions of the programmable inputs" in
chapter Digital inputs INPx (Page 145))
(misc.) (See Table:
Functions of
the inputs
CHANNEL NO.
- Index that is possibly assigned to the function
programmed in the previous parameter. Example: If
the input function is set to Cxx Commands menu
execution, and this input is to perform command
C07 in the Commands menu, then P12.n.02 must
OFF OFF / 1-99
CONTACT TYPE
– Select the contact type: NO (normally open) or
NO NO/NC
DELAY ON
– Contact closing delay for selected input.
s 0.05 0.00-600.00
DELAY OFF
– Contact opening delay for selected input
s 0.05 0.00-600.00