Auxiliary power supply: Terminal 53,54
Supply voltage U
s
100 - 240 VAC
Operating range 90 - 264 VAC
Power loss (max.) at 100 VAC: 5.3W
Interference strength against voltage dips at 240 VAC:
- without expansion modules ≤ 40 ms (at 110 VAC)
- with 3 expansion modules ≤ 20 ms (at 110 VAC)
Impulse withstand voltage U
imp
Power frequency withstand voltage
DC power supply: Terminal 26,27
Operating range of battery power supply
Current consumption (max.) 400 mA at 12 VDC
220 mA at 24 VDC
Voltage measuring inputs: Terminals 1-4 and 5-8
Nominal voltage U
e
(maximum)
600 VAC L-L (346 VAC L-N)
50 - 720 VAC L-L (30…415 VAC L-N)
Measuring method True RMS
Impedance of measuring input > 0.55 MΩ L-N
Single-phase, two-phase, or three-phase system
Measuring accuracy ± 0.25 %,
Impulse withstand voltage U
imp
Power frequency withstand voltage