MODBUS communication
10.4 Data library
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01
201
10.4.4 Status of the ATC (use with MODBUS function 03 and 04)
Address
Words
Function
Format
2210H
2
Status of the ATC (bit 0 - bit 31)
unsigned integer
The meaning of the 32 bits of the address 2210H can be viewed below:
Bit
Meaning
0 ATC in OFF mode
1
ATC in MAN mode
2
ATC in AUT mode
3
ATC in Test mode
4
Voltage Source 1 OK
5
Voltage Source 2 OK
6
Not used
7
Global alarm A
8
Global alarm B
9
Automatic test on Source 1 enabled
10
Automatic test on Source 2 enabled
11
Not used
12
Remote control
13
Clock in 100 ms
1431
Not used
10.4.5 Real-time clock (use with MODBUS function 04 and 06)
Address
Words
Function
Range
28F0H
1
Year
2000 - 2099
28F1H
1
Month
1 - 12
28F2H
1
Day
1 - 31
28F3H
1
Hours
0 - 23
28F4H 1 Minutes 0 - 59
28F5H
1
Seconds
0 - 59