Parameterization
9.4 Parameters
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01
177
9.4.10 P10 - Communications
This menu is divided into three sections for the integrated interface COM1 and for the
possible interfaces COM2 and COM3.
Note:
The integrated RS485 interface is permanently defined as COM1.
Designation on
ATC display
SERIAL
NODE
– Serial address (nodes) of the communication proto-
1 01-255
BAUD RATE
– Transmission speed of the communication port
bps 9600 1200
2400
4800
9600
19200
38400
57600
DATA
FORMAT
– Setting to 7 bits only possible for ASCII protocol.
8 bit - n 8 bit, no parity
8 bit, odd bit,
even
7 bit, odd
STOP BITS
1 1-2
PROTOCOL
– Choice of communication protocol
Mod-
bus RTU
Modbus RTU
Modbus ASCII
IP ADDRESS
IP address (not selectable for COM1)
– TCP / IP / coordinates for applications with Ethernet /
interface.
Note: Cannot be used with RS458 expansion module.
192.168.
1.1
000.000.000.000
–
255.255.255.255
SUBNET
MASK
Subnet mask (cannot be selected for COM1)
See parameter 10.n.06
0.0.0.0 000.000.000.000
–
TCP-IP PORT
TCP-IP port (cannot be selected for COM1)
1001 0-32000
CHANNEL
FUNCTION
Channel function role of the communication protocol
(cannot be selected for COM1)
Slave Slave
CLIENT/SERV
ER
Client / Server (cannot be selected for COM1)
– Enabling of the TCP-IP connection.
Server = Wait for connection of
a remote client. Client = Establishes the connection
Server Client
Server
REMOTE IP
ADDRESS
Remote IP address (cannot be selected for COM1)
– Coordinates for the connection with the remote serv-
er, if P16.n.10 is configured on client.
000.000.
000.000
000.000.000.000
–