Parameterization
9.4 Parameters
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01
161
9.4.1 P01 - Settings
Designation on ATC
display
LANGUAGE
– This parameter is used for setting the lan-
guage of the user interface.
English English
Italian
French Span-
ish
German
Portuguese
Polish
CLOCK SETTING
Setting of the real-time clock when switching
on the power supply of the ATC
– This parameter determines whether the
real-time clock is to be reset or not after each
OFF OFF
ON
MODE AT POWER
ON
Operating mode after power on
– This parameter determines which mode the
ATC6500 enters after switching on. It can
either be always switched on in the operating
mode OFF, or in the last operating mode
used before the device was switched off.
Previous OFF mode
previous mode
DISPLAY CONTRAST
– This can be used to adjust the contrast of
% 50 0-100
HIGH BACKLIGHT
LEVEL
– This parameter sets the bright LCD back-
% 100 0-100
LOW BACKLIGHT
LEVEL
– This parameter sets the dim LCD backlight-
% 25 0-50
LOW BACKLIGHT
DELAY
– This allows you to set a delay, after which
the ATC6500 switches to low backlighting.
s 180 5-600
DEFAULT PAGE
RETURN
– This parameter controls whether the device
switches to a default page defined under
P01.09 if no key is pressed within a specific
time. If this parameter is set to OFF, the
ATC6500 always remains on the last page to
s 300 OFF / 10/600
DEFAULT PAGE
Selection of default page
– This parameter is used to select a new
default page from the existing display pages
of the ATC6500. In connection with P01.08, a
switch is made to this page after a certain
Configura-
tion
(List with dis-
play pages)
MAIN PAGE TITLE
– You can enter any alphanumeric descrip-
SIEMENS
ATC6500
String 20 chr.