Parameterization
9.4 Parameters
3KC ATC6500 transfer control device
168 Manual, 05/2019, L1V30538268002A-01
9.4.6 P06 - Source Lines
This menu is divided into 2 sections for Source 1 (SRC1; SRC1 = Source 1) and Source 2
(SRC2).
P06
Qn, n = 12)
Designation on ATC
display
Description
Unit
Default
Range
P06.n.01
SOURCE
DESCRIPTION
Description of source
- This parameter enables the user to de-
fine any name for the sources.
This name then appears on the Overview
display page.
Qn (char*6)
P06.n.02
PRIORITY
Priority source
-
This parameter defines priority of the
source. If both sources should be availa-
ble, the source with priority 1 is regarded
as the priority source. If both sources
should have the same priority, Source 1 is
prioritized.
n 1/2
P06.n.03
SOURCE TYPE
Type of source
-
This parameter defines whether the con-
nected source is a generator or a network.
The corresponding diagram is then shown
on the Overview display page.
Network Network
Generator
P06.n.04
COOLING TIME
Generator cooling time
Maximum duration of the cooling cycle.
Time that elapses between the disconnec-
tion of load from the generator and the
engine actually stopping.
Note: If P06.n.03 is set to generator.
sec 120 1-3600