Connection
7.3 Connection of Siemens SENTRON switching devices
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01
105
7.3.3 Technical specifications of the Siemens SENTRON switching devices (IEC
only)
The following table lists the required data of the air circuit breakers and molded case circuit
breakers.
Note
Nevertheless, check the data of the circuit
breaker used against the corresponding catalog
or using the breaker manual.
Key features of the 3VA11 – 3VA14, 3VA20 – 3VA24
Product standard IEC
60947
IEC
60947
IEC
60947
IEC
60947
IEC
60947
IEC
60947
IEC
60947
IEC
60947
IEC
60947
Rated operational
voltage U
e
AC 50 /
[V AC] 600² 600² 600² 600² 600² 600² 600² 600² 600²
Rated operational
current I
n
at 50 °C
ambient tempera-
[A] 16
…160
16
…250
250
…400
400
…630
25
…100
25
…160
160
…250
250
…400
400
…630
Rated operational
[Hz] 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60
Short-time with-
stand current I
cw
at
[kA] 2
1
3
1
4.8
1
n.a. n.a. n.a. n.a. n.a. n.a.
Impulse withstand
voltage (U
imp
) of
[kV] 8 8 8 8 8 8 8 8 8
Impulse withstand
voltage (U
imp
) of
[kV] 4 4 4 4 4 4 4 4 4
Applies to 3VA switch disconnector
2
Due to maximum rated voltage U
n
of the ATC6500 controller of 600 V AC