Parameterization
9.4 Parameters
3KC ATC6500 transfer control device
182 Manual, 05/2019, L1V30538268002A-01
9.4.16 P16 - Counter CNTx
You can find more information on the counters in chapter Counters CNTx (Page 78).
P16
Cntn, n
=18)
Designation on
ATC display
Description
Unit
Default
Range
P16.n.01
COUNTER
SOURCE
Counter source
Signal that increments the counter (at the rising edge). This
may involve exceeding a threshold (LIMx) or enabling an ex-
ternal input (INPx) etc.
OFF OFF
ON
INPx
OUTx
LIMx
REMx
Axx
UAx
RALx
P16.n.02
CHANNEL NO.
Channel number (x)
Number of the channel x, with reference to the previous
parameter.
1 1-99
P16.n.03
MULTIPLIER
Multiplier
Multiplication factor. The counted pulses are multiplied by
this factor before they are displayed.
1 1-1000
P16.n.04
DIVIDER
Divider
Division factor. The counted pulses are divided by this factor
before they are displayed. If this value is not equal to 1, the
counter is shown with two decimal places.
1 1-1000
P16.n.05
DESCRIPTION
Description of the counter
Description of the counter. Freely selectable text, 16 charac-
ters.
CNTn (Text - 16
charac-
ters)
P16.n.06
UNIT OF
MEASURE
Unit of measurement
Measurement unit of the counter. Freely selectable text, 6
characters.
Umn (Text - 16
charac-
ters)
P16.n.07
COUNTER
SOURCE
RESET
Reset/source
Signal that resets the counter. As long as this signal is ena-
bled, the counter remains at zero.
OFF OFF
ON
INPx
OUTx
LIMx
REMx
Axx
UAx
RALx
P16.n.08
CHANNEL NO.
Channel number (x)
Number of the channel x, with reference to the previous
parameter.
1 1-99