Parameterization
9.4 Parameters
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01
181
9.4.15 P15 - User limit thresholds LIMx
You can find more information on the limit thresholds in chapter Limit threshold LIMx
(Page 75).
Designation
on ATC dis-
play
REFERENCE
MEASURE
- Defines which measurements of the ATC6500 the limit
threshold is applied to. For the list of reference measure-
ments, refer to chapter Limit threshold LIMx. (Page 75)
OFF See chapter
Limit thresholds
LIMx (Page 75)
REFERENCE
SOURCE
Source reference measurement
– If the reference measurement involves an electrical
measurement, this parameter specifies whether it refers to
OFF OFF
SRC1
SRC2
CHANNEL
NO.
– If the reference measurement is an internal multi-channel
measurement, the channel number is defined here.
1 OFF / 1-99
FUNCTION
– Defines the mode of operation of the limit threshold (see
chapter User limit threshold LIMx (Page 75))
MAX MAX
MIN
UPPER
THRESHOLD
– Defines the upper threshold obtained by multiplying the
value of P15.n.05 by the value of P15.n.06.
0 -9999 - + 9999
MULTIPLIER
x1 -100 -x10k
DELAY
– Upper threshold intervention delay.
sec 0 0.0-600.0
LOWER
THRESHOLD
– Defines the lower threshold obtained by multiplying the
value of P15.n.08 by the value of P15.n.09.
0 -9999 - + 9999
MULTIPLIER
x1 -100 - x10k
DELAY
sec 0 0.0 – 600.0
NORMAL
– Used for reversing the status of the threshold LIMn.
OFF OFF-ON
MEMORY
– Defines whether the threshold remains stored and must
be reset manually via the Commands menu (ON) or is
automatically reset (OFF).
OFF OFF-ON