Parameterization
9.4 Parameters
3KC ATC6500 transfer control device
166 Manual, 05/2019, L1V30538268002A-01
9.4.4 P04 - Battery
Note
Use of DC power supply
The following parameters are necessary only if you are using a DC power supply (see
chapter
Connecting the power supply (Page 83)).
P04
Designation on
ATC display
Description
Unit
Default
Range
P04.01
BATTERY
VOLTAGE
Nominal voltage of the battery
This parameter defines the voltage of the additional DC
supply of the ATC6500.
Note:
If this parameter is set to OFF, all alarms regarding
the DC supply, as well as the indicator for the battery volt-
age, are disabled.
V AUTO AUTO
12
24
48
OFF
P04.02
MAX. VOLTAGE
LIMIT
Maximum limit for battery voltage
This defines the upper limit threshold for the battery volt-
age
% 130 110-
140
P04.03
MIN. VOLTAGE
LIMIT
Minimum limit for battery voltage
This defines the lower limit threshold for the battery volt-
age
% 75 60-130
P04.04
MIN/MAX
VOLT.DELAY
Delay for minimum / maximum battery voltage
This parameter defines the delay for the mini-
mum / maximum battery voltage. If the voltage exceeds the
upper or lower limits from P04.02 and P04.03 for the peri-
od defined by this parameter, the corresponding alarms
are triggered.
s 10 0-120