Accessories
11.1 Expansion modules
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01
219
11.1.8 Technical Specifications 2DO
Power supply
Supply voltage
5 V DC (supplied through the ATC6500)
Current consumption (max.)
100 mA
Power loss (max.)
0.5 W
Relay outputs
Contact type
2x 1 CO contact
Rated contact current (IEC 60947-5-1) AC1 5 A 250 V
DC1 5 A 28 V
AC15 1.5 A 250 V
UL Rating (UL 508) B300, R300, 28 V DC 5A resistive, 250 V AC 5 A resis-
tive
Operational voltage (maximum)
250 V AC
Mechanical/electrical endurance (cycle)
3x10^6 / 1x10^5
Connecting terminals
Removable / plug-in
Cable cross-section (min-max)
0.22.5 mm
2
(AWG 28 ... 12)
Tightening torque
0.5 Nm (4.5 lbf-in)
Conductor temperature (min.)
75 °C
Insulation
Insulation voltage Ui
250 V AC
Impulse withstand voltage Uimp
- between the ATC and the outputs: 7.3 kV
- between 2 relay outputs:
2.5 kV
Operating frequency impulse withstand
voltage
- between the ATC and the outputs:
4 kV
- between 2 relay outputs:
1.5 kV
Ambient conditions
Operating temperature
-20+60 °C
Storage temperature
-30+80 °C
Relative humidity
< 80 % (IEC / EN 60068-2-70)
Maximum degree of pollution
2
Overvoltage category
3
Altitude of environment (max.)
2000 m
Enclosure
Enclosure material
Polyamide RAL7035
Degree of protection
IP20
Weight
50 g