5.1 Basic functions
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01
65
5.1.6.3 Alarm table
The features of the alarms can be modified using Menu P22. This can be selected from the
Setup menu. The alarms have the following features (for a definition of the features, please
refer to chapter Features of the alarms (Page 62)).
Code
Description
Ena-
bled
Only
AUT
Re-
tained
Global
alarm A
Global
alarm B
Lock
BRK 1
Lock
BRK 2
Siren
Inhi-
bition
Mo-
dem
No
LCD
A01 Voltage of the DC supply
too low
x x x x x
A02 Voltage of the DC supply
too high
x x x x x
A03 Source 1 circuit breaker
timeout
x x x x x x x
A04 Source 2 circuit breaker
timeout
x x x x x x x
A05 Source 1 wrong phase
sequence (SRC1)
x x x x x
A06 Source 2 wrong phase
sequence (SRC2)
x x x x x
A07 Load not powered timeout
x x x x x
A08
Emergency
x
x
x
x
x
A09 Source 1 breaker protection
trip
x x x x x x x
A10 Source 2 breaker protection
trip
x x x x x x x
A11 Breaker 1 (BRK1) with-
drawn
x x x x x x x x
A12 Breaker 2 (BRK2) with-
drawn
x x x x x x x x
A13 Generator Source 1 not
available
x x x x
A14 Generator Source 2 not
available
x x x x
A15 Maintenance hours Source
1
x x x
A16 Maintenance hours Source
2
x x x
A17 Maintenance operations
Breaker 1 (BRK1)
x x x
A18 Maintenance operations
breaker 2 (BRK2)
x x x
A19
Auxiliary voltage failure
x
x
x
x
A20
Tie breaker timeout (TRIP)
x
x
x
x
x
x
x
x
A21 Tripping of the protection
device of tie breaker TB
x x x x x x x