Functions
5.1 Basic functions
3KC ATC6500 transfer control device
66 Manual, 05/2019, L1V30538268002A-01
Code
Description
Ena-
bled
Only
AUT
Re-
tained
Global
alarm A
Global
alarm B
Lock
BRK 1
Lock
BRK 2
Siren
Inhi-
bition
Mo-
dem
No
LCD
A22
Tie breaker TB withdrawn
x
x
x
x
x
x
x
UA1
…8
User alarm UA1…8
Note
Inhibition function
The "Inhibition" function is not activated in the factory
settings but can be selected or
deselected by the user.
Procedure for enabling/disabling features:
To activate or deactivate the feature of an alarm, the option must be selected or deselected
for the corresponding alarm:
Alarm 01 Enabled feature activated
Alarm 01 Enabled feature deactivated
Press the or keys to jump to and fro between the individual alarms. Move between the
alarm features by pressing the and keys. The feature is selected or deselected by
pressing the key. The OFF key is used for closing the alarm table
See also
Parameterization via the user interface (Page 155)