Parameterization
9.4 Parameters
3KC ATC6500 transfer control device
180 Manual, 05/2019, L1V30538268002A-01
9.4.13 P13 - Digital Outputs
This menu is divided into 20 sections. These refer to 7 possible digital outputs
OUT1…OUT10 that can be managed directly by the ATC6500, and a further 9 outputs that
can be managed by the ATC6500 via the expansion modules.
Note: OUT5, OUT6 and OUT8 cannot be selected.
Designation on
ATC display
OUTPUT
FUNCTION
Function of the output OUTn
– Choice of function of the selected output
(misc.
)
(See Table:
Functions of
the outputs
CHANNEL NO.
- Index that is possibly assigned to the function programmed
in the previous parameter.
If the output function is set to the function Alarms
Axx, and this output is to be enabled when the Alarm A16
occurs, P13.n.02 must be set to the value 16.
OFF OFF / 1-99
OUTPUT
TYPE
– Sets the status of the output if the function assigned to it is
inactive: NOR = Output de-energized, REV = output ener-
NOR NOR / REV
9.4.14 P14 - Miscellaneous
Designation on
ATC display
MAINTENANC
E INTERVAL
Maintenance interval in hours
– Defines in hours the programmed time interval for sched-
uled maintenance. If this parameter is set to OFF this
maintenance interval is disabled.
H OFF OFF / 1-
99999
MAINTENANC
E COUNTER
Maintenance interval operations
– Defines the programmed time interval for scheduled
maintenance in number of operating cycles. If this parame-
ter is set to OFF this maintenance interval is disabled.
OFF OFF
1-99999
OPERATING
MODE
OUTPUT
– Defines in which operating mode the output programmed
to the function is to be enabled. For example, if this parame-
ter is set to M/O, the operating mode output is enabled
when the ATC6500 is in the MAN or OFF mode.
OFF OFF
O
M
M - O
A