Parameterization
9.4 Parameters
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01
167
9.4.5 P05 - Acoustic alarms
P05
Designation on
ATC display
Description
Unit
Default
Range
P05.01
ALARM SOUND
MODE
ALARM SOUND MODE
- This parameter defines the behavior of the
sirens. These can be enabled for alarms (see
chapter Alarms (Page 61))
OFF = The siren is disabled
KEYBOARD = The siren is enabled and can
only be disabled by pressing a key on the
ATC
TIMED = The siren remains enabled for the
period set in parameter P05.02
REPEAT = The siren remains enabled for
the period set in parameter P05.02, then
waits for 3-times as long as this and starts
again. This process is repeated cyclically.
TIMED OFF
KEYBOARD
TIMED
REPEAT
P05.02
SOUND ON
ALARM TIME
Duration of siren in case of alarm
- The duration of the siren on occurrence of
an alarm is set by this parameter
sec 30 OFF / 1-600
P05.03
SOUND BEFORE
START
Duration of siren before generator start
- This
parameter defines whether and for how long
the siren is active before a generator is start-
ed.
sec OFF OFF / 1-60
P05.04
SOUND ON
REMOTE CNT.
Duration of siren by communication
- This parameter determines whether the
siren is to be enabled when the ATC is re-
motely controlled via communication. The
duration of the siren can also be defined.
sec OFF OFF / 1-60
P05.05
SOUND ON SRC1
FAIL
Duration of siren failure Source 1
- If Source 1 fails, this parameter enables the
siren and its duration to be defined.
sec OFF OFF / 1-60
P05.06
SOUND ON SRC2
FAIL
Duration of siren failure Source 2
- If Source 2 fails, this parameter enables the
siren and its duration to be defined.
sec OFF OFF / 1-60
P05.08
ACOUSTIC OUT.
DEVICE
Type of signal tone
-
This parameter defines which acoustic
signals are enabled.
Buzzer +
Siren
OFF
SIREN
BUZZER
BUZZER + Siren
P05.09
BUZZER ON KEY
PRESS
Buzzer on pressing a button
- This parameter enables a sound to be acti-
vated on pressing a button. It is also possible
to define by how many ms the sound should
be delayed.
sec 0.15 OFF / 0.01-0.5

Table of Contents