Connection
7.2 General connection drawings
3KC ATC6500 transfer control device
92 Manual, 05/2019, L1V30538268002A-01
Terminal
Parameter code
Settings
43 (INP4)
P12.4.01 Function of the input INP4
Source 1 breaker protection (Trip 1)
44 (INP5) P12.5.01 Function of the input INP5 Source 2 breaker protection (Trip 2)
55 (OUT1)
P13.1.01 Function of the output OUT1
Open Source 1 breaker
57 (OUT2) P13.2.01 Function of the output OUT2 Close Source 1 breaker
58 (OUT3)
P13.3.01 Function of the output OUT3
Open Source 2 breaker
60 (OUT4)
P13.4.01 Function of the output OUT4
Close Source 2 breaker
See also
Connection of the power supply for the ATC6500 (Page 83)
7.2.3 Transfer with remotely operated transfer switching equipment
Remote transfer switching equipment (RTSE) is already mechanically interlocked due to its
design.
Note
Implementation of the power supply
More information on implementing the power
supply of the ATC6500 via the inputs 53, 54
and
/ or the inputs 26, 27 can be found in chapter Connection of the power supply (Page 83).