Connection
7.2 General connection drawings
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01
93
The following basic parameters must be set for the circuit diagram shown:
P02.01 System configuration
- P02.22 Management of the tie breaker
OFF
Changeover pulse or changeover continuous
40 (INP1) P12.1.01 Function of the input INP1 Source 1 breaker closed (feedback 1)
P12.2.01 Function of the input INP2
Source 2 breaker closed (feedback 2)
P13.1.01 Function of the output OUT1
P13.2.01 Function of the output OUT2
P13.3.01 Function of the output OUT3
Open Source 1 and Source 2