MODBUS communication
10
The following chapter contains:
General information on MODBUS
MODBUS RTU protocol
MODBUS ASCII protocol
MODBUS functions
Data library
10.1 General information on MODBUS
The ATC6500 supports the MODBUS RTU, MODBUS TCP and MODBUS ASCII protocols
via the following interfaces:
Integrated RS485 interface on the device
Expansion module Ethernet (3KC9000-8TL75)
Via these two interfaces it is possible to modify the status of the ATC6500, as well as of the
parameters using third-party supervision software (scada) or by means of other devices such
as PLCs. The communication via MODBUS TCP is only possible via the Ethernet expansion
module (3KC9000-8TL75).
Setting the communication parameters
The parameters can be set by means of the P10 - Communications (Page 177) menu.
10.2 MODBUS RTU protocol
If the MODBUS RTU protocol is used, the following structure must be observed:
T1
T2
T3
Address
(8 bit)
Function
(8 bit)
Data
(N x 8 bit)
CRC
(16 bit)
T1
T2
T3
Address: Contains the serial address of the slave target device.
Function: Contains the code of the function that is performed by the slave.
Data: Contains the data that is sent to the slave, or the data of a query received by the slave
(maximum length 80, 16-bit register).
CRC: This is used for an integrity check. If a message is corrupted by electric noise or
interference, the CRC field enables the ATC6500 to detect the error and thus ignore the
message.