Functions
5.1 Basic functions
3KC ATC6500 transfer control device
62 Manual, 05/2019, L1V30538268002A-01
5.1.6.1 Features of the alarms
Various features can be assigned to each alarm, including the user alarms (UAx see chapter
User alarms (Page 67)).
Alarms enabled (Enable)
General enabling of the alarm. If an alarm has not been enabled, the procedure is as if
the alarm did not exist.
AUT only (Aut)
The alarm can only be triggered if the ATC6500 is in automatic mode.
Retention alarm (Retent)
Remains stored, even after the triggering cause has been removed.
Global alarm A (Glb-A)
Activates the output which is assigned to this function.
Global alarm B (Glb-B)
Activates the output which is assigned to this function.
Lock breaker 1 (Lock 1)
On occurrence of the alarm, no further commands are sent to Breaker 1.
Lock breaker 2 (Lock 2)
On occurrence of the alarm, no further commands are sent to breaker 2.
Siren (Siren)
Activates the output assigned to this function, as configured in the table of alarms
Inhibition (inhibit)
The alarm can be temporarily deactivated by activating a programmable input with the
alarm inhibit function.
Modem
The alarm is sent via the modem (SMS or FTP)
No LCD (No LCD)
The alarm is managed normally, but not shown on the display.