Connection
7.2 General connection drawings
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01
97
7.2.6 Transfer with 3 circuit breakers
With electrical interlock between breaker 1 (BRK1) and breaker 2 (BRK2)
Code
Description
BRK1 / BRK2
Breaker BRK1 / 2
TB
Tie breaker TB / NPL
In the drawing shown above an electrical interlock is achieved by means of the auxiliary
switch interlock. A mechanical interlock can be applied in addition.
Note
Implementation of the power supply
More information on implementing the power supply of the ATC6500 via the inputs 53, 54
and
/ or the inputs 26, 27 can be found in chapter Connection of the power supply (Page 83).