Operation
8.2 Inputs and outputs of the ATC6500
3KC ATC6500 transfer control device
150 Manual, 05/2019, L1V30538268002A-01
Some functions require another numeric parameter. This is specified by parameters by
means of an index.
Note
Use of an index
An ind
ex is used if additional functions are to be used as a source for the output.
For example, an output can function as a source for a counter or for a user alarm.
On replacement or subsequent modification of the modules, attention mus
t be paid to the
addre
ssing (see chapter Addressing of the expansion modules with digital inputs/outputs
(Page
152)).
8.2.5 Table of functions of the digital outputs
The table below lists all functions that can be assigned to the programmable digital outputs
OUTx.
Function
Designation on the ATC6500
Description
Disabled
Disabled
Output disabled
Configurable
Configurable
Free configuration by the user.
Close Source 1 contactor/breaker
L1 close
Command to close the contactor/breaker of Source 1.
Open Source 1 contactor/breaker L1 open Command to open the breaker of Source 1 with possi-
ble spring load.
Close Source 2 contactor/breaker
L2 close
Command to close the contactor/breaker of Source 2.
Open Source 2 contactor/breaker L2 open Command to open the breaker of Source 2 with possi-
ble spring load.
Open Source 1 and Source 2 L1-L2 open Open both breakers / neutral position of the transfer
switching equipment with motor operator.
Undervoltage release breaker 1 Min V coil 1 Controls the undervoltage release by opening break-
er 1 before the spring load cycle.
Undervoltage release breaker 2 Min V coil 2 Controls the undervoltage release by opening break-
er 2 before the spring load cycle.
Control Generator 1 Start generator 1 Control of the Start / Stop remote control of the gen-
erator on Source 1.
Control Generator 2 Start generator 2 Control of the Start / Stop remote control of the gen-
erator on Source 2.
ATC ready ATC ready ATC in automatic mode, without alarms, ready to
switch.
Global alarm A Global alarm A Output enabled in the presence of any alarm with the
property "Global alarm A"
Global alarm B Global alarm B Output enabled in the presence of any alarm with the
property "Global alarm B"
Source 1 voltage status SRC1 VOLTAGE OK This output is enabled if all conditions for the connec-
tion of the load to Source 1 have been met.
Source 2 status SRC2 VOLTAGE OK This output is enabled if all conditions for the connec-
tion of the load to Source 2 have been met.