Operation
8.2 Inputs and outputs of the ATC6500
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01
149
The following outputs are installed on the ATC6500:
Designation
Pin
Description
Technical specifica-
tions
Recommended cable
cross-section
Digital outputs
OUTx
19
Digital output OUT7 1 x CO contact
8 A AC1 250VAC
8 A DC1 30VDC
1.5 A AC15 250VAC
0.2 - 2.5 mm
2
(24 - 12 AWG) acc. to
UL508: 0.75 -
2.5 mm
2
(18 - 12 AWG)
20
21
30
Digital output OUT9 1 x CO contact
8 A AC1 250VAC
8 A DC1 30VDC
1.5 A AC15 250VAC
31
32
33
Digital output OUT10 1 x CO contact
8 A AC1 250VAC
8 A DC1 30VDC
1.5 A AC15 250VAC
34
35
55 Digital output OUT1 1 x NO contact
12 A AC1 250VAC
1.5 A AC15 250VAC
8 A DC1 30VDC
56 Control terminal for pins
55 and 57
57 Digital output OUT2 1 x NO contact
8 A AC1 250VAC
1.5 A AC15 250VAC
8 A DC1 30VDC
58 Digital output OUT3 1 x NO contact
12 A AC1 250VAC
1.5 A AC15 250VAC
8 A DC1 30VDC
59 Control terminal for pins
58 and 60
60 Digital output OUT4 1 x NO contact
8 A AC 1 250VAC
1.5 A AC 15 250VAC
8 A DC1 30VDC
The function of the outputs can be selected from preprogrammed functions.
The setting is made via the Menu P13 (see chapter P13 - Digital outputs (Page 180)). Every
output can be configured for normal or reverse function (NOR or REV).