Accessories
11.1 Expansion modules
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01
221
Connection of NPN open collector
11.1.10 Technical Specifications 2DI 2DO
Power supply
Supply voltage
5 V DC (supplied through the ATC6500)
Current consumption (max.)
200 mA
Power loss (max.)
1.0 W
Digital inputs
Number of digital inputs
2
Input type
Negative
Input current
7 mA
Maximum frequency 2000 Hz (if the input is configured as a counter)
50 Hz (if input is configured as status)
Input signal delay
50 ms
Impulse withstand voltage U
imp
4 kV
Operating frequency impulse with-
stand voltage
2 kV
Control terminal COM
Auxiliary power supply at control
terminal COM
5 V DC
Relay outputs
Contact type
2x 1 NO contact
Rated contact current
(IEC 60947-5-1)
AC1 5 A 250 V
DC1 2 A 30 V
AC15 0.75 A 250 V
UL Rating C300, 2 A 30 V DC, 5 A 250 V AC pilot duty
Operational voltage (maximum)
250 V AC
Mechanical/electrical endurance
(cycle)
3x10^6 / 1x10^5
Impulse withstand voltage U
imp
4 kV
Insulation voltage U
i
250 V AC
Operating frequency impulse with-
stand voltage
2 kV