Connection
7.3 Connection of Siemens SENTRON switching devices
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01
107
7.3.4 Typical operating times of the Siemens SENTRON switching devices (IEC only)
The following typical operating times can be achieved with the ATC and Siemens circuit
breakers.
Note
Checking
The tables below contain typical operating values. Check the operating times of the
respective total installation under real conditions.
Note:
The operating times of the tie breaker can be obtained from the manual or the catalog of the
relevant circuit breaker. Note the additional interlock time for the tie breaker control in
accordance with parameter P02.30 (see chapter P02 (Page 162)).
Operating times of the 3VA
Time I-O-II (for min parameter)*
* includes the minimum delay time from Source 1 to Source 2 of 100 ms (see parameter P07.n.02)
Time I-O-II (for min
ms 2100 260 2100 260 3200 3200 170
* includes the minimum delay time from Source 1 to Source 2 of 100 ms (see parameter P07.n.02)
Operating times of the 3WL
Time II-O ms 20 73 73 73
Time I-O-II (for min parame-
ms 170 253 273 273
* includes the minimum delay time from Source 1 to Source 2 of 100 ms (see parameter P07.n.02)