MODBUS communication
10.4 Data library
3KC ATC6500 transfer control device
200 Manual, 05/2019, L1V30538268002A-01
③ Key press simulation
The following values must be sent to the address 2F0AH in order to simulate the
corresponding key press:
1 Key MAN
3 << key
④ Execution of the Commands menu
The following values between 0 and 15 must be sent to the address 2FF0H in order to
execute the corresponding command:
Reset maintenance operations 1
Reset maintenance operations 2
Reset status limit threshold LIMx
Reset hours counter Source 1
Reset hours counter Source 2
Reset hours counter Breaker 1
9 Reset hours counter Breaker 2
11 Reset event log
Restore default parameters
Save parameters in backup memory
Reload parameters from backup memory
Simulates priority source failure