Connection
7.7 Connection of 3WT8 air circuit breakers
3KC ATC6500 transfer control device
134 Manual, 05/2019, L1V30538268002A-01
Note
Implementation of the power supply
More information on implementing the power su
pply of the ATC6500 via the inputs 53, 54
/ or the inputs 26, 27 can be found in chapter Connection of the power supply (Page 83).
Note
Mechanical interlock
A mechanical interlock of the circuit breakers can be applied in addition.
Note
Expansion modules
For additional functions, expansion modules with inputs/outputs can be attached if necessary
(see chapter
Expansion modules (Page 209)).
You can find more information on the technical specifications of the circuit breaker in the
Operating Manual of the SENTRON 3WT8 air circuit breaker
(https://support.industry.siemens.com/cs/ww/en/view/33272206
).
P02.01 System configuration
P02.22 Management of the tie breaker (TB)
Breaker pulse or breaker continuous
P12.1.01 Function of the input INP1
Source 1 breaker closed (feedback 1)
P12.2.01 Function of the input INP2
Source 2 breaker closed (feedback 2)
P12.3.01 Function of the input INP3
Source 1 breaker protection (Trip 1)
P12.4.01 Function of the input INP4
Source 2 breaker protection (Trip 2)
P13.1.01 Function of the output OUT1
P13.2.01 Function of the output OUT2
P13.3.01 Function of the output OUT3
P13.4.01 Function of the output OUT4