Parameterization
9.4 Parameters
3KC ATC6500 transfer control device
164 Manual, 05/2019, L1V30538268002A-01
P02
Designation on ATC
display
Description
Unit
Default
Range
P02.32
POST-TRANSFER
TIME 1
Post-transfer time Load 1
After a transfer between the sources, this parame-
ter defines when the Post-transfer Load 1 output is
enabled. For more information, see chapter
Table of
functions of the digital outputs (Page 150).
s OFF OFF /
1…1000
P02.33
PRE-TRANSFER
TIME 2
Pre-transfer time Load 2
Delay between enabling the output Pre-transfer
Load 2 and the actual shutting down of the load. An
output must be parameterized with the function Pre-
transfer time Load 2 for this purpose. For more
information, see chapter
Table of functions of the
digital outputs (Page 150).
s OFF OFF /
1…1000
P02.34
POST-TRANSFER
TIME 2
Post-transfer time Load 2
After a transfer between the sources, this parame-
ter defines when the Post-transfer Load 2 output is
enabled. For more information, see chapter
Table of
functions of the digital outputs (Page 150).
s OFF OFF /
1…1000
P02.37
CONT. COM. TB IN
OFF
Continuous command of tie breaker TB in OFF
mode
This specifies the behavior of the opening/closing
command outputs in the continuous signal mode, if
the ATC6500 is in the OFF mode. Used in applica-
tions with contactors.
OFF Opens the command outputs
NOC Leaves the outputs unchanged
NOC OFF
NOC
P02.39
TB. EN. CONDITION
Enabling of tie breaker TB
This parameter enables you to specify how and
whether the tie breaker is to be controlled.
OFF = The tie breaker is controlled normally
Other selection = The tie breaker can only be con-
trolled if the selected condition is met.
Example:
On selecting INPx, the tie breaker can
only be controlled if the corresponding input is ac-
tive.
OFF OFF
INPx
OUTx
LIMx
REMx
Ax
UAx
TIMx
P02.40
CHANNEL NO.
Function index
Index that is possibly assigned to the function
programmed in the previous parameter. Example:
The tie breaker TB should only be controllable if the
input 4 has been enabled: P02.39 = INPx P0240 =
4
OFF OFF / 1-99
P02.43
INTERLOCK TB
Interlock time of tie breaker TB
Delay that elapses between disconnection of the
tie breaker and the opening command for the
source breakers.
sec 6 0.1 - 1800