12.2 Transfer sequence
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01
233
Failure of secondary source (Source 2)
Note
In addition to the various delay times for limit violation, the transfer is also influenced by
the interlock times under parameter P07.n.02.
The tie breaker TB is always closed after the breakers of the sources. The time delay for
closing of the tie breaker is defined under P02.30.
See also
Application D: 2S - 1T - AI (Page 24)
Parameters (Page 160)