Technical specifications
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01
239
Relay outputs OUT7, OUT9, OUT10: Terminals 19-21, 30-32, 33-35
Rated contact current AC1 8A 250V
AC15 1.5A 250V
UL Rating B300
30 VDC 1 A auxiliary duty
Mechanical/electrical endurance (cycle)
Impulse withstand voltage U
imp
Power frequency withstand voltage OUT7, OUT9,
3 kV
<80 % (IEC / EN 60068-2-78)
Maximum degree of pollution
Connecting terminals Removable / plug-in
Cable cross-section (min-max)
0.2 …2.5 mm2 (AWG 24 ... 12)
Cable cross-section (min-max) acc. to UL 508
0.75 …2.5 mm2 (AWG 18 ... 12)
Degree of protection IP40 at front (can be increased to IP65 by using IP protective seal),
Certifications and approvals
The following standards are complied with:
Complies with standards IEC / EN 61010-1, IEC / EN 61010-2,
IEC / EN 61000-6-3, IEC / EN 61000-6-4,
UL marking Use 60°C/75°C copper (CU) conductor only
AWG Range: 18 - 12 AWG stranded or solid
Field Wiring Terminals Tightening Torque:
4.5lb.in
Flat panel mounting on a Type 1 or 4X enclosure
Note: This product is designed for environment A. Its use in a Class B environment can lead to unwanted electromagnetic
problems. Consideration should be given to possible measures for mitigating the electromagnetic radiation.