EasyManua.ls Logo

Siemens SENTRON ATC6500 - Page 86

Siemens SENTRON ATC6500
256 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Connection
7.1 Connection of the power supply for the ATC6500
3KC ATC6500 transfer control device
84 Manual, 05/2019, L1V30538268002A-01
Technical specification of the ATC6500 power supply
Designation
Pin
Feature
Recommended cable cross-section
DC power supply
26
-
12 - 48 V DC (7.5 - 57.6 V DC) 0.2 - 2.5 mm
2
(24 - 12 AWG)
According to UL508:
0.75 - 2.5 mm
2
(18 - 12 AWG)
27
+
Auxiliary power supply
53
L
100 - 240 V AC (90 - 264 V AC)
110 - 250 V DC (93.5 - 300 V DC)
54
N
The following devices can be used to ensure that the continuous supply of power to the
ATC6500 can be implemented:
Use of a DC source / battery
Use of a dual network connection
Use of an uninterruptible power supply (UPS)
Use of contactors

Table of Contents

Related product manuals