Technical specications
• for "0" to "1" *
7 ms
• for "1" to "0" **
3 ms
Wiring two outputs in parallel No
Switching frequency
• with resistive load
100 Hz
• with inductive load
2 Hz
* Response time of the relay
** Release time of the relay
Approvals
ATEX II 2 G(1) GD and I M2
Ex eb ib mb IIC T4 Gb
Ex eb ib mb I Mb
KEMA 07 ATEX 0180
IECEx IECEx KEM 07.0059
INMETRO
BR-Ex eb ib mb IIC T4 Gb;
BR-Ex eb ib mb I Mb
FM Class I, Zone 1, AEx eb ib mb IIC T4;
Ex eb ib mb IIC T4
NI, Class I, DIV. 2, GP A,B,C,D T4
Class II, III, GP E, F, G
cULus
Process Cont. Eq. for Use in HAZ.LOC.
Class I, Zone 1, AEx eb ib mb IIC T4;
Ex eb ib mb IIC T4
Class I, DIV. 2, GP. A,B,C,D T4
CCC Ex e ib mb IIC T4 Gb
UKCA DEKRA 21UKEX0025
Switching capacity and service life of contacts
With an external protective circuit, the contacts will last longer than specied in the following
table.
Digital electronic modules
13.3 Digital electronic module 2 DO Relay UC60V/2A
ET 200iSP
Operating Instructions, 11/2022, A5E00247483-AK 333