Technical specifications
14.1 Standards, approvals and safety notes
Distributed I/O system
System Manual, 09/2019, A5E03576849-AJ
273
PROFIBUS standard
The PROFIBUS interfaces of the ET 200SP distributed I/O system are based on IEC 61158
Type 3.
IO-Link standard
The ET 200SP distributed I/O system is based on IEC 61131-9.
Shipbuilding approval
Classification societies:
ABS (American Bureau of Shipping)
BV (Bureau Veritas)
DNV-GL (Det Norske Veritas - Germanischer Lloyd)
LRS (Lloyds Register of Shipping)
Class NK (Nippon Kaiji Kyokai)
KR (Korean Register of Shipping)
CCS (China Classification Society)
RINA (Registro Italiano Navale)
Use in industrial environments
The ET 200SP distributed I/O system is suitable for use in industrial environments. It meets
the following standards for this type of use:
Requirements on interference emission EN 61000-6-4: 2007 + A1: 2011
Requirements on immunity EN 61000-6-2: 2005
Use in mixed areas
Under specific prerequisites you can use the ET 200SP distributed I/O system in a mixed
area. A mixed area is used for residential purposes and for commercial operations that do
not significantly impact the residential purpose.
If you want to use the ET 200SP distributed I/O system in residential areas, you must ensure
that its radio frequency interference emission complies with limit class B in accordance with
EN 61000-6-3. Suitable measures for observing these limits for use in a mixed area are, for
example:
Installation of the ET 200SP distributed I/O system in grounded control cabinets
Use of filters in the supply lines
An additional individual acceptance test is also required.