Technical specifications
14.2 Electromagnetic compatibility
Distributed I/O system
276 System Manual, 09/2019, A5E03576849-AJ
Pulse-shaped disturbance variables of motor starters
The following table shows the electromagnetic compatibility of the ET 200SP motor starters
with regard to pulse-shaped interference.
Table 14- 2 Pulse-shaped disturbance variables
Pulse-shaped disturbance variable
Burst pulses (fast transients) in
accordance with IEC 61000-4-4,
tested with 5 kHz.
±2 kV (24 V supply cables)
±2 kV (500 V AC infeed*)
±1 kV (signal cable <30 m)
3
If you mount the motor starter to the right of a 15 mm or 20 mm I/O module or immediately next to a
head module, use a dummy module. You will find further information in "Selecting motor starters with
a suitable BaseUnit (Page 40)."
High-energy single pulse (surge) in
accordance with IEC 61000-4-5
500 V AC infeed
±2 kV conducted interference - phase to
ground
±1 kV conducted interference - phase to phase
24 V supply cable:
±1 kV conducted interference - phase to
ground
**)
±0.5 kV conducted interference - phase to
**)
3
**) An RC circuit is not required for hybrid switching devices.
If higher values (2 kV (phase to ground) or 1 kV (phase to phase) are required, you will need an addi-
tional external protective circuit (see Designing interference-free controllers
(http://support.automation.siemens.com/WW/view/en/59193566) function manual).
Sinusoidal disturbance variables
The tables below show the electromagnetic compatibility of the ET 200SP distributed I/O
system with regard to sinusoidal disturbance variables.
● RF radiation
Table 14- 3 Sinusoidal disturbance variables with RF radiation
RF radiation according to IEC 61000-4-3/NAMUR 21
Electromagnetic RF field, amplitude-modulated
Corresponds to degree
of severity
80 to 1000 MHz; 1.0 to 2.0 GHz
3
● RF coupling