Technical specifications
14.5 Mechanical and climatic environmental conditions
Distributed I/O system
284 System Manual, 09/2019, A5E03576849-AJ
Climatic environmental conditions
The table below shows the permissible climatic environmental conditions for the ET 200SP
distributed I/O system:
Table 14- 10 Climatic environmental conditions
Environmental conditions
Permissible range
Comments
Temperature:
horiz. mounting position:
vertical mounting position:
-30 °C to 60 °C
-30 °C to 50 °C
The lower permissible ambient temperature was extended for
the ET 200SP system to -30 °C. Differences may exist for spe-
cific modules and depending on the mounting position and, if
applicable, load. Detailed information on this is described in the
technical specifications of the respective equipment manual.
The product data sheets with daily updated technical specifica-
tions can be found on the Internet
(https://support.industry.siemens.com/cs/ww/en/ps/td
) at Indus-
try Online Support. Enter the article number or the short de-
scription of the desired module on the website.
Permitted temperature
change
10 K/h -
Relative humidity
from 10 to 95%
Without condensation or icing.
Barometric pressure from 1140 to 795 hPa Corresponds to an altitude of -1000 to 2000 m.
Note the following section "Using the distributed IO system
ET 200SP over 2000 m above sea level".
Pollutant concentration ANSI/ISA-71.04 severity
level G1; G2; G3
-
SIPLUS products based on ET 200SP are offered for reliable operation under heavy to
extreme operating conditions.
Using the distributed IO system ET 200SP over 2000 m above sea level
The maximum "operating height above sea level" depends on the module and is described in
the technical specifications of the respective module. The product data sheets with daily
updated technical specifications can be found on the Internet
(https://support.industry.siemens.com/cs/ww/en/ps/td
) at Industry Online Support. Enter the
article number or the short description of the desired module on the website.
For altitudes > 2000 m, the following constraints apply to the maximum specified ambient
temperature:

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C