Parameter Data Type Default setting Meaning WinCC Tag
QCUR_WH BOOL FALSE 1=current high
LIMIT warning
reached
N
QCUR_WL BOOL FALSE 1=current low lim‐
it warning reached
N
QEM_START BOOL FALSE SIMOCODE DP 0.4:
1=emergency
start active
N
QENSDCS BOOL TRUE 1=enable internal
updating of record
130/131/133
Y
QERR BOOL FALSE 1=Program error Y
QERR_RCS BOOL FALSE 1=error reading
control/signal data
(record 130)
N
QERR_RSD BOOL FALSE 1=error reading
statistic data (re‐
cord 131)
N
QER_RSDST WORD 16#00 Error status - read‐
ing statistic data
(record 131)
N
QERR_WSD BOOL FALSE 1=error writing
statistic data (re‐
cord 133)
Y
QER_WSDST WORD 16#00 Error status - writ‐
ing statistic data
(record 133)
N
QER_RCSST WORD 16#00 Error status - read‐
ing control/signal
data (record 130)
N
QERR_WSD BOOL FALSE 1=error writing -
statistic data (re‐
cord 133)
Y
QG_FLT BOOL FALSE SIMOCODE DP 0.6:
general fault
Y
QG_WRN BOOL FALSE SIMOCODE DP 0.7
AND NOT DP 0.3:
general warning
Y
QLOCOP BOOL FALSE 1=operator ena‐
bled for input
LOCAL/REMOTE
Y
QLTA BOOL FALSE SIMOCODE DP 0.4:
lock time active
Y
QMAN_AUT BOOL FALSE 1=AUTO; 0=MAN‐
UAL
Y
QMAN_MOP BOOL FALSE 1=MANUAL-
LINKED; 0=MAN‐
UALOPERATOR
Y
Parameter
A.2Block Parameter Of SIMO_CHN
SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2
94 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE DP and is the answer not in the manual?

Siemens SIMOCODE DP Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE DP
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals